Litres per second /Air volumes
Technical information – CoolCats ACR recommended air volumes
Flexible Duct Sizing Guide
| MAX RECOMMENDED AIR QUANTITY (l/s) | FLEXIBLE DUCT DIA (mm) |
|---|---|
| 44 l/S | Ø 150 |
| 92 l/S | Ø 200 |
| 170 l/S | Ø 250 |
| 275 l/S | Ø 300 |
| 385 l/S | Ø 350 |
| 503 l/S | Ø 400 |
| 636 l/S | Ø 450 |
| 785 l/S | Ø 500 |
| 950 l/S | Ø 550 |